ACM Aluminum CORFLEX* II

CORFLEX* II RA90 (–40°C) XLPE 600 Volts
ACM Aluminum Conductors

SINGLE ALUMINUM CONDUCTOR

Size AWG
or
kcmil

Approximate Diameter

Approx Net Cable Weight Connectors
(Nexans
 Catalogue No.)
Minimum
Bending
Radius
Ampacity
30°C
Ambient

(amps)

(CE Code
Table 3)**

Over Sheath   Over PVC Jacket Without Jacket With PVC
 Jacket
mm in mm in kg/km lbs/kft kg/km lbs/kft Dry
Location
Type D
Wet or
Hazardous
Location
Type W
mm in
1/0 (18) 19.1 .75 21.8 .86 331 223 454 305 20D3 20W3 203 8 190
2/0 (18) 19.6 .77 22.4 .88 380 255 506 340 20D3 20W3 203 8 220
3/0 (18) 20.3 .80 23.1 .91 435 292 566 380 20D3 20W3 229 9 255
4/0 (18) 20.8 .82 23.4 .92 497 334 640 430 20D3 20W3 229 9 300
250 (35) 24.1 .95 26.9 1.06 604 406 759 510 25D3 25W3 254 10 330
300 (35) 25.1 .99 27.7 1.09 687 462 848 570 25D3 25W3 254 10 375
350 (35) 25.3 1.00 27.9 1.10 756 508 930 625 25D3 25W3 254 10 415
400 (35) 29.7 1.17 32.3 1.27 928 624 1116 750 30D4 30W4 305 12 450
500 (35) 30.3 1.19 33.0 1.30 1074 722 1281 861 30D4 30W4 305 12 515
600 (58) 35.1 1.38 37.6 1.48 1326 891 1548 1040 35D5 35W5 356 14 585
750 (58) 35.7 1.40 38.3 1.51 1561 1049 1802 1211 35D5 35W5 360 14 670
1000 (58) 40.3 1.59 43.5 1.71 2025 1361 2358 1584 40D5 40W5 381 15 800
1250 (91) 45.7 1.80 48.0 1.89 2529 1700 2820 1895 45D6 45W6 457 18 905

**Click here for single conductor cable direct buried ampacity.

THREE ALUMINUM CONDUCTORS

Size AWG
or
kcmil

    Approximate Diameter

Approx Net Cable Weight Connectors
(Nexans
 Catalogue No.)
Minimum
Bending
Radius
Ampacity
30°C
Ambient

(amps)

(CE Code
Table 4)***

Over Sheath Over PVC Jacket Without Jacket With PVC
 Jacket
mm in mm in kg/km lbs/kft kg/km lbs/kft Dry
Location
Type D
Wet or
Hazardous
Location
Type W
mm in
6 (7) 20.8 .82 23.4 .92 321 216 454 305 20D3 20W3 229 9 55#
4 (7) 24.1 .95 26.9 1.06 425 286 580 390 25D3 25W3 254 10 65
2 (7) 29.2 1.15 31.8 1.25 641 431 826 555 30D4 30W4 305 12 95#
1 18) 33.5 1.32 36.3 1.43 816 548 1027 690 35D5 35W5 330 13 105
1/0 (18) 35.1 1.38 37.6 1.48 925 622 1146 770 35D5 35W5 356 14 120
2/0 (18) 38.9 1.53 41.7 1.64 1141 767 1391 935 40D5 40W5 381 15 145
3/0 (18) 40.6 1.60 43.2 1.70 1310 881 1570 1055 40D5 40W5 406 16 165
4/0 (18) 43.7 1.72 46.2 1.82 1566 1053 1845 1240 45D6 45W6 432 17 185#
250 (35) 48.5 1.91 51.3 2.02 1990 1337 2299 1545 50D8 50W8 483 19 215
300 (35) 50.3 1.98 53.1 2.09 2248 1511 2575 1730 50D8 50W8 483 19 240
350 (35) 56.4 2.22 59.2 2.33 2560 1720 2924 1965 N/A N/A 533 21 260
400 (35) 56.4 2.22 59.2 2.33 2813 1890 3177 2135 N/A N/A 533 21 290
500 (35) 63.0 2.48 65.8 2.59 3441 2312 3847 2585 N/A N/A 610 24 330

***Click here for 3 conductor cable direct buried ampactiy

FOUR ALUMINUM CONDUCTORS

Size AWG
or
kcmil

 Approximate Diameter

Approx Net Cable Weight Connectors
(Nexans
 Catalogue No.)
Minimum
Bending
Radius
Ampacity
30°C
Ambient

(amps)

(CE Code
Table 4)****

Over Sheath   Over PVC Jacket Without Jacket With PVC
 Jacke
mm in mm in kg/km lbs/kft kg/km lbs/kft Dry
Location
Type D
Wet or
Hazardous
Location
Type W
mm in
6 (7) 23.9 .94 26.4 1.04 435 292 588 395 25D3 25W3 254 10 55#
4 (7) 25.7 1.01 28.2 1.11 543 365 707 475 25D3 25W3 254 10 65
2 (7) 33.0 1.30 36.1 1.42 885 595 1094 735 35D5 35W5 330 13 95#
1 18) 35.6 1.40 38.1 1.50 1489 1000 1265 850 35D5 35W5 330 13 105
1/0 (18) 39.4 1.55 41.9 1.65 1274 865 1525 1025 40D5 40W5 356 14 120
2/0 (18) 41.1 1.62 43.7 1.72 1471 989 1734 1165 40D5 40W5 381 15 145
3/0 (18) 44.2 1.74 46.7 1.84 1749 1175 2031 1365 45D6 45W6 406 16 165
4/0 (18) 48.8 1.92 51.6 2.03 2130 1431 2441 1640 50D8 50W8 432 17 185#
250 (35) 56.4 2.22 59.2 2.33 2501 1680 2865 1925 N/A N/A 483 19 215
300 (35) 54.4 2.22 59.2 2.33 2836 1905 3200 2150 N/A N/A 533 21 240
350 (35) 63.0 2.48 65.8 2.59 3293 2212 3698 2485 N/A N/A 610 24 260
400 (35) 63.0 2.48 65.8 2.59 3627 2437 4033 2710 N/A N/A 610 24 290
500 (35) 71.1 2.80 73.9 2.91 4796 3223 5253 3530 N/A N/A 686 27 330

Insulation Colour Code:

1 Conductor - Black
3 Conductors - Black, Red, White #14 to #2
  Black Insulation, white printed numbers #1 and larger
4 Conductors - Black, Red, Blue, White #14 to #2
  Black Insulation, white printed numbers #1 and larger

C.E. Code Rule 12-712(3).
****Assuming 4th conductor is the neutral of a balanced 3-phase 4 wire system. Other sizes available upon request.
#For 3-wire 120/240 and 120/208 volt residential services or sub-services, the allowable ampacity for sizes #6 and #2 AWG shall be 60 and 100 amperes respectively. In this case the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.
See Accessories for Hub, Knockout and Aluminum Clip Sizes. 