Armoured Cables

ACWU90 (–40°C) XLPE 
600 volts 90° C


ACM Aluminum Conductors

Description
One to four compact ACM aluminum conductors with low temperature Exelene* cross-linked polyethylene insulation (RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single conductor cables have copper concentric bonding wire. Conductor assembly is wrapped and enclosed in an interlocked aluminum armour with an overall low acid gas and low flame spread PVC jacket (LAG/LFS) with FT4 and AG14 rating.
#8 and larger are H.L. rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III Hazardous Locations.
CSA Spec C22.2 No. 51-95(R1999)
CSA File #LL23462 Class 5811 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable

Application
For exposed and concealed wiring in dry or wet locations and where exposed to the weather.
For use in ventilated, non-ventilated and ladder type cable trays in wet and dry locations. 
For direct earth burial (with protection as required by Inspection Authority).
For service entrance above or below ground.
For use in hazardous locations with approved connectors.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.


ONE STRANDED CONDUCTOR (plus bonding wire)
Size
 AWG or
kcmil
Insulation
Thickness
Bonding Wire
Size
AWG
Approximate
Diameter 
Approximate Net Cable
Weight
Ampacity**
30°C 
Ambient
(amps)
Armour PVC Jacket
mm in mm in mm in kg/km lbs/kft
1/0 (18) 1.40 .055 18.9 0.74 21.7 0.85 563 378 190
2/0 (18) 1.40 .055 20.7 0.81 23.1 0.91 690 464 220
3/0 (18) 1.40 .055 21.6 0.85 24.3 0.96 761 511 255
4/0 (18) 1.40 .055 23.1 0.91 25.6 1.01 848 570 300
250 (35) 1.65 .065 24.9 0.98 27.3 1.08 1007 677 330
300 (35) 1.65 .065 26.1 1.03 28.6 1.13 1098 738 375
350 (35) 1.65 .065 27.8 1.10 30.6 1.20 1265 850 415
400 (35) 1.65 .065 28.8 1.14 31.4 1.23 1338 900 450
500 (35) 1.65 .065 31.3 1.23 34.0 1.34 1619 1088 515
600 (58) 2.03 .080 34.0 1.34 36.7 1.45 1843 1239 585
750 (58) 2.03 .080 1/0  36.8 1.47 39.5 1.56 2210 1485 670
1000 (58) 2.03 .080 1/0  40.7 1.60 43.4 1.71 2660 1787 800
##1250 (91) 2.41 .095 2/0  47.3 1.87 50.6 1.99 3735 2507 905
##1500 (91) 2.41

.095

3/0 

51.4 2.02 54.7 2.16 4355 2925 1020

Insulation Colour Code:  Black

*Ampacity in accordance with Table #3 of the Canadian Electrical Code Part #1 (2002).
  For single conductor direct burial ampacity table click here.

##Conductors are compressed stranding not compact.


THREE STRANDED CONDUCTORS (plus bonding wire)
Size
 AWG or
kcmil
Insulation
Thickness
Bonding Wire
Size
AWG
Approximate
Diameter
Approximate Net Cable
Weight
Ampacity*
30°C 
Ambient
(amps)
Armour PVC Jacket
mm in mm in mm in kg/km lbs/kft
6 (7) 1.14 .045 8 (7) 20.6 0.81 23.6 0.93 500 335 55#
4 (7) 1.14 .045 6 (7) 23.1 0.91 25.9 1.02 618 415 65
3 (7) 1.14 .045 6 (7) 24.4 0.96 27.2 1.07 673 452 75
2 (7) 1.14 .045 6 (7) 25.9 1.02 28.7 1.13 771 518 95#
1 (18) 1.40 .055 4 (7) 28.9 1.14 31.7 1.25 941 632 105
1/0 (18) 1.40 .055 4 (7) 31.0 1.22 33.5 1.32 1074 722 120
2/0 (18) 1.40 .055 4 (7) 33.0 1.30 35.8 1.41 1235 830 145
3/0 (18) 1.40 .055 4 (7) 35.8 1.41 38.3 1.51 1444 970 165
4/0 (18) 1.40 .055 4 (7) 38.6 1.52 41.9 1.65 1746 1173 185#
250 (35) 1.65 .065 2 (7) 42.2 1.66 45.5 1.79 2165 1455 215
300 (35) 1.65 .065 2 (7) 45.7 1.80 48.8 1.92 2661 1788 240
350 (35) 1.65 .065 2 (7) 48.3 1.90 51.6 2.03 2958 1989 260
400 (35) 1.65 .065 2 (7) 50.3 1.98 53.6 2.11 3234 2173 290
500 (35) 1.65 .065 1 (18) 54.9 2.16 58.2 2.29 3767 2531 330
600 (58) 2.03 .080 1 (18) 60.4 2.38 64.5 2.54 4561 3065 370
750 (58) 2.03 .080 1/0 (18) 65.7 2.59 70.0 2.74 5423 3644 405

Insulation Colour Code:  Black, Red, White

*Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1 (2002).  
For 3 conductor direct buried ampacity table click here.

# For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. In these cases the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.


FOUR STRANDED CONDUCTORS (plus bonding wire)
Size
 AWG or
kcmil
Insulation
Thickness
Bonding Wire
Size
AWG
Approximate
Diameter Over
Approximate Net Cable
Weight
Ampacity**
30°C 
Ambient
(amps)
Armour PVC Jacket
mm in mm in mm in kg/km lbs/kft
6 (7) 1.14 .045 8 (7) 22.6 0.89 25.6 1.01 583 392 55#
4 (7) 1.14 .045 6 (7) 25.4 1.00 28.7 1.13 774 520 65
3 (7) 1.14 .045 6 (7) 26.9 1.06 29.4 1.16 818 550 75
2 (7) 1.14 .045 6 (7) 28.7 1.13 31.2 1.23 932 626 95#
1 (18) 1.40 .055 4 (7) 32.0 1.26 34.8 1.37 1143 768 105
1/0 (18) 1.40 .055 4 (7) 34.3 1.35 36.8 1.45 1323 889 120
2/0 (18) 1.40 .055 4 (7) 36.6 1.44 39.1 1.54 1533 1030 145
3/0 (18) 1.40 .055 4 (7) 39.4 1.55 42.4 1.67 1839 1236 165
4/0 (18) 1.40 .055 4 (7) 42.4 1.67 45.7 1.80 2168 1457 185#
250 (35) 1.65 .065 2 (7) 47.2 1.86 50.5 1.99 2897 1947 215
300 (35) 1.65 .065 2 (7) 50.2 1.98 53.5 2.11 3289 2210 240
350 (35) 1.65 .065 2 (7) 53.0 2.09 56.3 2.22 3612 2427 260
400 (35) 1.65 .065 2 (7) 55.6 2.19 58.9 2.32 3966 2665 290
500 (35) 1.65 .065 1 (18) 60.4 2.39 64.5 2.54 4834 3248 330
600 (58) 2.03 .080 1 (18) 67.0 2.64 70.9 2.79 5725 3847 370
750 (58) 2.03 .080 1/0 (18) 72.9 2.87 76.7 3.02 6860 4610 405

Insulation Colour Code:  Black, Red, Blue, White

**Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1 (2002).  Assuming the 4th conductor in a 4/c cable is the neutral of a balanced 3 phase 4 wire system.
For direct buried ampacity click here.

# For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. In these cases the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.

*Registered Trade Mark of Nexans Canada Inc.